Conduit Fill Calculator — NEC Chapter 9
Select conduit type, enter conductor sizes and counts — get an instant fill percentage, pass/fail result, and minimum conduit size. Works for EMT, IMC, RMC, and PVC. Mixed conductor sizes supported. Free, no account needed.
The Fill Rules — NEC Chapter 9, Table 1
NEC Chapter 9, Table 1 sets maximum fill percentages based on the number of conductors in the conduit:
These percentages apply to the conduit's total internal cross-sectional area from NEC Table 4. For mixed wire sizes, sum conductor cross-sectional areas from Table 5 (THHN areas used here) and compare to the 40% fill area for your conduit type and trade size.
Grounds occupy physical space in the conduit and must be included in the fill. Add them as a separate wire group in the calculator using the appropriate AWG.
EMT vs IMC vs RMC vs PVC
All trade sizes ("½ inch", "¾ inch") have different actual interior areas depending on wall thickness. EMT has the largest interior area for a given trade size — meaning you can fit more conductors. RMC has the thickest wall and smallest interior. You may need a larger trade size in RMC compared to EMT for the same conductor package.
- EMT — thin wall, most common for interior commercial. Largest interior area per trade size.
- IMC — intermediate wall. ~90% of EMT's interior area at most sizes.
- RMC — thick wall, required for service entrance and high-abuse locations. Smallest interior area.
- PVC Schedule 40 — non-metallic, direct burial and wet locations. Area similar to EMT.
- PVC Schedule 80 — thicker wall than Sch 40, smaller interior. Common where exposed to physical damage.
Worked Examples
Example 1 — 3 × 12 AWG THHN in ½" EMT
Example 2 — Mixed sizes, 1" EMT
4 × 10 AWG + 2 × 12 AWG + 1 × 12 AWG ground = 7 conductors total, 40% rule applies.
Example 3 — 200A service, 2" RMC
2 × 2/0 THHN ungrounded + 1 × 2/0 neutral + 1 × 4 AWG ground = 4 conductors.
FAQ
Why is the 2-conductor limit (31%) more restrictive than 3+ (40%)?
Two large conductors side by side in a round conduit are harder to pull than those same conductors plus a smaller third. The geometry of how round conductors pack inside a round conduit changes with count — 31% reflects the pulling force required for two conductors through a run with standard bends.
Can I use the NEC Annex C tables instead of this calculator?
NEC Annex C provides pre-calculated maximum counts for same-size same-insulation conductors in each conduit type and trade size. For mixed sizes, you must use the Table 4 + Table 5 manual method — which is what this calculator does.
Does conduit fill and ampacity derating interact?
Yes — they're separate calculations. A conduit that passes the 40% fill rule with many current-carrying conductors may still require ampacity derating per NEC 310.15(C)(1). Always do the derating calculation separately when more than 3 current-carrying conductors are present.
Why does DesignedWire use THHN areas?
THHN/THWN is the most common insulation type for conductors pulled in conduit. If you're using XHHW or another insulation type, the conductor areas are slightly different — check NEC Table 5 for exact values. XHHW typically has a larger OD than THHN, so THHN areas give a slightly optimistic result for XHHW conductors.
NEC Chapter 9 conduit fill is one of the most frequently tested calculation topics on state licensing exams — most states require you to know the 40%/31%/53% rules and how to use Tables 4 and 5 for mixed conductor sizes. Use this calculator to check your hand-worked answers. The conduit fill guide has three full worked examples including a 200A service run.